ha44e/475-4 ha4/465-4
福州天行健provide原厂gea-bock船用压缩机及压缩机零部件
福州天行健节能科技有限公司提供欧美日船舶原装进口品牌零部件
ha single-stage compressors
the ha-system - the best solution for deep-freezing!
special features:
- direct intake with external ventilation
- suction gas intake directly into the compressor
- motor cooled by an integrated ventilation unit
this reduces the compressed gas temperature and thus expands the range of application while at the same time increasing capacity (deep-freeze, r22, r404a). at the same time, the compressor is physically separated from the compressor, with advantages particularly in the case of motor damage.
technical data
hax44e/475-4
application refrigeration & ac
compressor refrigeration capacity 7.43 kw
power consumption 4.62 kw
current draw (400 v) 12.30 a
mass flow 0.056 kg/s
at following operating condition:
refrigerant r404a, r507
reference temperature dew point
evaporating temperature -35.0 °c
condensing temperature 40.0 °c
supply frequency 50 hz
voltage 400 v
suction gas temperature 20 °c
subcooling (outside cond.) 0 k
number of cylinders / bore / stroke 4 / 55 mm / 50 mm
displacement 50/60 hz (1450/1740 ¹/min) 41,30 / 49,60 m³/h
voltage 1) 380-420v y/yy -3- 50hz pw
440-480v y/yy -3- 60hz pw
winding divided into 50% / 50%
max. working current 2) 15.2 a
max. power consumption 2) 7.6 kw
starting current (rotor blocked) 2) 87.0 / 149.0 a
motor protection int69 g
protection terminal box / ha-fan ip 66 / ip 44
voltage ha-fan 230 v - 1 - 50/60 hz, 140 w
protection terminal box ip 66
weight 174 kg
max. permissible overpressure (g) (lp/hp) 3) 19 / 28 bar
connection suction line sv 35 mm - 1 3/8 "
connection discharge line dv 28 mm - 1 1/8 "
lubrication oil pump
oil type r134a, r404a, r407a/c/f, r448a, r449a, r450a, r513a bocklub e55
oil type r22 bocklub a46
oil charge 2,7 ltr.
oil sump heater 230 v - 1 - 50/60 hz, 160 w
dimensions length / bbbbb / height 717 / 361 / 408 mm
sound power level lwa 4) 81 db(a) @ -35 °c / 40 °c
sound pressure level lpa 4) 68 db(a) @ -35 °c / 40 °c
scope of supply
semi-hermetic four-cylinder reciprocating compressor with drive motor for part winding start
380-420 v y/yy - 3 - 50 hz
440-480 v y/yy - 3 - 60 hz
single-section compressor housing with hermetically integrated electric motor
oil pump
motor is cooled by an integrated ventilator with air deflection hood.
230 v - 1 - 50/60 hz, ip44, 140 w, 0,71 a
winding protection with ptc resistor sensors and electronic trigger unit int69 g
115-230 v ac, 50/60 hz, ip00
rear bearing flange prepared for oil differential pressure sensor delta-p ii
possibility of connection of oil level controllers esk, ac r or carly
possibility of connection of oil level controllers traxoil 5)
possibility for connection of oil pressure safety switch mp54
oil charge:
ha: bocklub a46
hax: bocklub e55
sight glass
pressure relief valve
suction and discharge line valve
inert gas charge
4 anti-vibration pads enclosed
accessories
start unloader by means of a ess (electronic soft start), 400 v - 3 - 50/60 hz, ip20 (connection clamps ip00) for installation in switch cabinet 6)
digital capacity regulator dcr14 230 v - 1 - 50/60 hz, ip65
1 digital capacity regulator = 50% residual capacity 7)
cylinder cover prepared for digital capacity regulator
oil sump heater
230 v - 1 - 50/60 hz, 160 w, ip66
ptc heater self-regulating
thermal protection thermostat per cylinder cover 7)
oil pressure safety switch mp54 230 v - 1 - 50/60 hz, ip20 6)
oil differential pressure sensor delta-p ii 220-240 v - 1 - 50/60 hz 8)
connection piece suction and discharge valve in welding design 9)
usb converter for int69 g diagnose 6)
oil temperature sensor (pt1000, for external bbbbuation) 7)
int69 g diagnose 115-230 v ac, 50/60 hz, ip00 (int69 g not applicable)
dp-modbus gateway 115-230 v ac, 50/60 hz, ip00 including adapter cable 6)
modbus-lan gateway 230 v ac, 50/60 hz, ip00 6)
intermediate flange for suction valve on right seen from oil pump in conjunction with capacity regulator 6)
step protection
special voltage and/or frequency (on request)
notes
1) tolerance (± 10%) relates to the mean value of the voltage range. other voltages and current types on request
all data are based on voltage rms values
pw = part winding, motors for part winding starting
(no start unloaders required)
designs for y/d on request
2) - the stated value for the max. power consumption is valid for the adjusted power supply.
- starting current (rotor blocked):
part winding (pw) motors: winding 1 / winding 1 2
delta/star (δ/y) motors: δ / y
- take account of the max. operating current / max. power consumption for designing fuses, supply lines and safety devices. fuse: consumption category ac3.
3) lp = low pressure
hp = high pressure
4) declared dual-number noise emission values are in accordance with iso 4871. the corresponding uncertainty to the sound power level is kwa = 2,5 db and to the sound pressure level is kpa = 2,5 db. the values are valid for 50 hz with the refrigerant r404a at the standard rating points according to en 12900.
a-weighted sound power level lwa (re 1 pw), in decibel. to determine the values, measurement bbbbbbs of the iso 3740 standard with accuracy class 2 or higher were used .
a-weighted sound pressure level lpa (re 20 µpa), in decibel. the values are calculated from the sound power level in accordance with iso 11203: lpa = lwa - q2 at a distance of d = 1m to the reference box.
5) only with additional adapter possible
6) enclosure
7) mounted
8) enclosure (screw-in part mounted)
9) on request